Integrated Components
Filter · Fan Motor · Coil · Jet Nozzle
Product Overview
Designed specifically for large spaces such as industrial plants and logistics warehouses, the unit integrates a filter, fan motor, coil and jet nozzle.
A nylon filter is included as standard, with an optional oil-mist filter for environments affected by oily fumes. Bottom return air and side return air configurations are available to suit different installation layouts.
Filter · Fan Motor · Coil · Jet Nozzle
Nylon Filter
Oil-Mist Filter
Bottom Return Air · Side Return Air
Air Supply Design
Reduces unit width by approximately one-third and increases vehicle clearance by 45% compared with conventional cabinet-type jet units.
Provides wider air distribution and may reduce the number of required units by up to 50%.
Supports wall-mounted installation for a cleaner and more integrated appearance.
Suspended Installation
Suspended indoor unit installation eliminates the need for air ducts, simplifies product selection and installation, and can reduce the construction period by up to 50%.
Long installation cycles and complex connections with conventional hydronic systems.
Complicated floor layouts that make floor-mounted units difficult to install.
Overhead crane rails and structural obstacles that complicate ductwork and water-pipe installation.
The unit can be quickly suspended from bridge structures, crane rails or ceiling supports. Its clean appearance integrates naturally into large industrial spaces while providing dependable indoor comfort.
Engineered Details
Insulated panels, integrated drainage, certified heat exchange and a profile-free cabinet structure support reliable performance and practical maintenance in high-ceiling applications.




Oil-Mist Filtration
For processing workshops and other environments with oil mist, an optional low-resistance washable oil-mist filter provides a dedicated filtration solution.
The filter uses an air-permeable mesh with a multi-layer structure combining separation and collection layers. It efficiently captures oil-mist particles and dust, offers partial self-cleaning capability, and can be repeatedly washed and reused.
The side-access design allows fast removal and replacement for easier maintenance.
Technical Data
Model data for preliminary selection of the TFD-SC high-ceiling dedicated air handling unit.
| Model | TFD042GCWSC | TFD055GCWSC | TFD074GCWSC | TFD085GCWSC | |
|---|---|---|---|---|---|
| Airflow | m³/h | 4200 | 5500 | 7400 | 8500 |
| Rated Cooling Capacity | kW | 42 | 62 | 80 | 84 |
| Rated Heating Capacity | kW | 46 | 66 | 84 | 90 |
| Water Flow | L/s | 1.8 | 3.0 | 3.8 | 4.2 |
| Water Resistance | kPa | 33 | 62 | 57 | 78 |
| Power Supply | — | 380V 3N~50Hz | |||
| Motor Power - Speed | kW-P | 1.1-4 | 1.5-4 | 2.2-4 | 3.0-4 |
| Filter | — | Nylon (Std)/Oil Mist (Opt) | |||
| Dimensions | long / mm | 2360 | 2860 | 3460 | 3460 |
| width / mm | 1080 | 1080 | 1180 | 1180 | |
| height / mm | 700 | 780 | 870 | 870 | |
| Weight | kg | 200 | 240 | 320 | 320 |
| Chilled Water Pipe Diameter | — | DN40 | DN40 | DN50 | DN50 |
| Condensate Pipe Diameter | — | DN25 | DN25 | DN25 | DN25 |
Project Support
If you are evaluating TICA High-Ceiling Dedicated Air Handling Unit for a project, share your building type, required capacity, climate conditions and control requirements with our team.
To ensure your inquiry reaches us promptly, we recommend contacting us through WhatsApp using the contact panel on the right. You can also visit our official Alibaba.com store to discuss system selection and request a project quotation.
Visit Our Official Alibaba.com Store